Product details:
Miniature multi9 circuit breaker, current rating 25 amps, number of poles 2, maximum voltage 480 volts, high tripping current 350 amps, low current trip setting 250 amps, din mounted miniature circuit protectors and breakersmulti 9 breakers feature factory-calibrated overload curves. Withstand 6000v impulse. Rated for 20, 000 tripping operation cycles. Line and load side box lug terminals pressure plate type are suitable for use with multiple wires. Din rail or panel mount with accessory front bracket. Wire size: max. 4 Awg cu for 0.5 To 25a models, max. 2 Awg cu for 30 to 63a models.b curve magnetic trip between 3.2 And 4.8 Times rated current computer, electronic, and generator applications c curve magnetic trip between 7 and 10 times rated current ac and 7 to 14 times for dc general purpose applications d curve magnetic trip between 10 and 14 times rated current motors, transformers, and similar applicationsul 1077 supplementary protection within equipmentmust use with circuit breaker or fuse. Recognized components for applications permitting supplementary protectors. Not a substitute for ul 489 models, and must be used in conjunction with branch circuit protection when connecting to external devices. 10ka ir at 240vac 5ka ir at 480y/277vac.